Tewaycell 48V/51.2V LiFePO4 Batteries – Integration Guide for Victron Systems

Tewaycell 48V/51.2V LiFePO4 Batteries – Integration Guide for Victron Systems

How‑to: Connect Tewaycell 48V / 51.2V LiFePO4 Batteries to Victron GX via CAN‑bus BMS

Tewaycell 48 V / 51.2 V LiFePO4 storage batteries feature native CAN‑bus BMS communication at 500 kbit/s, designed to work with Victron GX‑based energy storage systems. Once communication is established and DVCC is set to Forced‑on, the Victron GX establishes data communication with the Tewaycell battery.

> Do not use a generic lead-acid charging profile as a substitute for the battery-specific configuration. For a supported managed-battery installation, configure the system to use the BMS-provided operating limits as specified in the applicable integration instructions. Do not rely on the battery’s protective shutdown as a normal charge-control method.

What hardware you will need

1. Tewaycell 48 V / 51.2 V LiFePO4 battery pack
2. Victron GX device 
3. Type‑B VE.Can to CAN‑bus BMS communication cable

Important: Do not use standard CAT5/CAT6 Ethernet patch cables. Standard ethernet pin‑out does not match battery RJ45 CAN port and may cause communication failure or hardware damage.

Download our full step‑by‑step commissioning document here:

👉 Tewaycell Battery‑ Victron CAN‑bus BMS Setup Guide

Key prerequisites before commissioning

- Battery CAN communication baud rate is fixed at 500 kbit/s
- On battery screen: Parameter Settings → Set CAN Prot → select VICTRON protocol
- Multi‑battery parallel setup: Set unique DIP‑switch CAN address for every battery on the same CAN bus (address range: 1‑15)
- Common signal GND connection (pin 2 on battery CAN RJ45) is mandatory for stable CAN communication. Missing GND is one of the top causes for unstable or intermittent communication faults.

Quick overview of main configuration steps

1. Battery side preparation

1.1 Power‑on the battery, wait for full BMS startup completion
1.2 Select VICTRON CAN protocol in battery parameter menu
1.3 Configure unique DIP‑switch CAN address for each battery in multi‑unit parallel banks

2. Cable connection

Plug Type‑B CAN‑bus cable between battery CAN‑RJ45 port and the BMS‑Can port on Victron GX device.

Wiring mapping inside Type‑B cable:

  Battery CAN‑H (pin 4) ↔ Victron BMS‑Can CAN‑H
  Battery CAN‑L (pin 5) ↔ Victron BMS‑Can CAN‑L
  Battery GND (pin 2) ↔ Victron signal GND

Note: This guide applies exclusively to factory‑built Tewaycell 48 V / 51.2 V LiFePO4 batteries. DIY battery packs using JK‑BMS feature different pin assignments and require separate wiring instructions from the BMS supplier.

3. GX device settings

3.1 In GX Settings → Services → BMS‑Can port → CAN‑bus profile, choose CAN‑bus BMS (500 kbit/s) profile.
3.2 Go to Settings → DVCC and set DVCC: Forced on. Enable Limit charge current.

> Note: Max charge current setting shall never exceed the hardware maximum charge‑current value specified in battery datasheet.

3.3 After configuration, verify the battery appears in the GX device list and battery parameters become visible before closing DC breaker of inverter‑charger.

4. VEConfigure ESS‑Assistant setup

Connect to GX via Remote Console or MK3‑USB cable, open VEConfigure tool:

4.1 Save existing inverter configuration file as backup.
4.2 Under Charger tab, enable Lithium batteries and select Lithium Iron Phosphate (LiFePO4) batteries.
4.3 Add ESS (Energy Storage System) assistant. In ESS wizard select option: System uses LiFePO4 batteries with other type of BMS.
4.4. Fill in total battery bank capacity, configure sustain voltage and keep default Dynamic cut‑off / Restart offset parameters.
4.5. Send settings to hardware, complete device reboot to activate ESS assistant.

How it works in operation

Once communication is established and DVCC Forced‑on is active:
Victron system respects these BMS‑provided limits, automatically adjusting inverter‑charger and solar‑charger behaviour to protect lithium‑ion cells.

> Never run the system with fixed lead‑acid battery profiles; this bypasses BMS protective limits and risks battery damage.

Common troubleshooting tips

If battery does not show up inside GX device list, check these high‑probability points:

- RJ45 cable plugged into battery RS485 port or GX VE.Can port (wrong port)
- CAN‑H / CAN‑L swapped, or ordinary Ethernet patch‑cable used
- Missing signal GND (pin 2) connection
- Wrong CAN‑bus profile selected on GX
- Duplicate DIP‑switch CAN address among parallel batteries
- Battery CAN protocol not switched to VICTRON
- Power‑on sequence: battery should finish BMS startup before powering‑up GX
- Other foreign CAN‑bus devices sharing the same CAN bus

For full fault‑check list, please refer to our downloadable setup guide document.

Important safety notes

- Perform all wiring work with DC breakers open and battery powered‑off. Dangerous DC voltage remains on battery terminals even when inverter is turned off.
- For multi‑battery parallel installation: DC bus is paralleled; CAN communication must follow daisy‑chain topology, star topology is unsupported.
- Always keep a copy of original Victron inverter configuration before modifying settings inside VEConfigure.
- Please also consult official Victron documentation for GX / VEConfigure background knowledge.